E+H Ultrasonic Level Transmitter Setup​

May 12, 2025

 

​Maintenance Requirements​

  •    The level transmitter ​​requires no special maintenance​​.

​Basic Configuration​

  1.   ​​Initial Setup​​:

    •    Press the ​​E​​ (Enter) key to access the ​​primary menu​​.
    •    Select ​​"Basic Setup"​​ and press ​​E​​.
  2.   ​​Tank Geometry​​:

    •    In the ​​secondary menu​​, choose the tank shape (e.g., ​​"Flat Ceiling"​​ for flat-top tanks).
    •    Press ​​E​​ to confirm.
  3. ​  Medium Type​​:

    •    In the ​​tertiary menu​​, select the medium type (e.g., ​​"Liquid"​​).
    •    Press ​​E​​.
  4. ​  Surface Condition​​:

    •    In the ​​quaternary menu​​, select the surface state (e.g., ​​"Turb Surface"​​ for turbulent liquid surfaces).
    •    Press ​​E​​.
  5. ​  ​Empty Calibration​​:

    •    Set the ​​"Empty Calibr."​​ distance (e.g., ​​5.500 m​​ – distance from flange to tank bottom).
      •   Press ​​↓​​ or ​​↑​​ to adjust the value.
    •    Press ​​E​​ to confirm.
  6.   ​​Blind Zone (Blocking Distance)​​:

    •    Set ​​"Blocking Dist"​​ (e.g., ​​0.35 m​​) to define the non-measurement zone near the sensor.
    •    Press ​​E​​.
  7.   ​​Full Calibration​​:

    •    Set the ​​"Full Calibr."​​ span (e.g., ​​5.15 m​​ = 5.500 m – 0.35 m).
      •   Press ​​↓​​ or ​​↑​​ to adjust.
    •    Press ​​E​​ repeatedly to return to the primary menu.
    •    Press ​​↓ + ↑​​ simultaneously to exit to the display screen.

Display Unit Configuration​

  1. ​  Access Menu​​:

    •    Press ​​E​​ to enter the primary menu.
    •    Navigate to ​​"Linearisation"​​ using ​​↓​​ or ​​↑​​, then press ​​E​​.
  2.   ​​Unit Selection​​:

    •    In the secondary menu, select ​​"Level DU"​​ and choose ​​meters (m)​​ as the unit.
    • ​   Note​​:
      •   ​​"Ullage CU"​​ displays the level as a percentage (e.g., 50% = half-full).